1752 - 600 Volt, HDPE, Single Pair, Overall Shield, Unarmored
Description
- Conductor7-strand bare copper, Class B
- Primary insulation0.025 inch (0.6 mm) for 16 AWG; 0.030 inch (0.8 mm) for 14 AWG, polyethylene
- Color codeBlack and white
- Group identificationEach pair numbered
- Pair shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
- JacketBlack FR-PVC
Application
- Excellent dielectric properties
- Good chemical and long-term moisture resistance
- Non-flame retardant (does not pass IEEE 383 or IEC 332)
- 600 volt rated insulation per ICEA
Bending Radius
- 6 x d (d = overall diameter)
Cable Type
- Single pair shielded
Other Options
- Manufactured in accordance with ICEA. Also available to IEC, BS standards or customized configurations.
- Various metric and AWG size conductors
- Special color coding of insulation and jacket materials
- LDPE or CPE jacket
The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.
Electrical Properties | Units | Conductor Size | |||||||||
16 AWG / 1.3 mm² | 14 AWG / 2.1 mm² | 1.5 mm² | 2.5 mm² | ||||||||
Resistance [R] | Ω/Mft | Ω/km | 4.2 | 13.7 | 3.6 | 11.9 | 2.6 | 8.6 | 2.2 | 7.2 | |
Mutual Capacitance | |||||||||||
Type 1752 | pF/ft | pF/m | 25 | 82 | 24 | 77 | 26 | 85 | 27 | 89 | |
L/R Ratio | μH/Ω | 23 | 27 | 36 | 42 | ||||||
Inductance [L] | μH/ft | μH/m | 0.19 | 0.62 | 0.20 | 0.65 | 0.19 | 0.62 | 0.18 | 0.60 |
Part Number | Pairs | Nominal O.D. | Weight | Jacket Thickness | ||||||
in | mm | lb/ft | kg/m | mils | mm | |||||
Conductor Size: 16 AWG / 1.3 mm² | ||||||||||
1752-68F03 | 1 | 0.314 | 8.0 | 0.058 | 0.087 | 45 | 1.14 | |||
Conductor Size: 14 AWG/ 2.1 mm² | ||||||||||
1752-48L03 | 1 | 0.364 | 9.2 | 0.079 | 0.118 | 45 | 1.14 | |||
Conductor Size: 1.5 mm² | ||||||||||
1752-N8F03 | 1 | 0.322 | 8.2 | 0.062 | 0.092 | 45 | 1.14 | |||
Conductor Size: 2.5 mm² | ||||||||||
1752-PBL03 | 1 | 0.405 | 10.3 | 0.091 | 0.135 | 45 | 1.14 |