1852 - 600 Volt, PVC, Single Pair, Overall Shield, Unarmored
Description
- Conductor7-strand bare copper, Class B
- Primary insulation0.030 inch (0.8 mm) for 16 AWG; 0.030 inch on all gauges
- Color codeBlack and white
- Group identificationEach pair numbered
- Pair shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
- JacketBlack FR-PVC
Application
- UL listed as TC
- Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
- NEC Article 336
- 600 volt rated insulation
Bending Radius
- 6 x d (d = overall diameter)
Cable Type
- Single pair shielded
Other Options
- Manufactured in accordance with UL. Also available to ICEA, IEC, CSA, BS standards or customized configurations.
- Various metric and AWG size conductors
- Special color coding of insulation and jacket materials
The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.
Electrical Properties | Units | Conductor Size | |||||||||
16 AWG / 1.3 mm² | 14 AWG / 2.1 mm² | 1.5 mm² | 2.5 mm² | ||||||||
Resistance [R] | Ω/Mft | Ω/km | 4.2 | 13.7 | 2.7 | 8.6 | 3.6 | 11.9 | 2.2 | 7.2 | |
Mutual Capacitance | |||||||||||
Type 1852 | pF/ft | pF/m | 43 | 142 | 45 | 147 | 49 | 161 | 52 | 170 | |
L/R Ratio | μH/Ω | 24 | 27 | 36 | 42 | ||||||
Inductance [L] | μH/ft | μH/m | 0.2 | 0.66 | 0.19 | 0.64 | 0.18 | 0.62 | 0.18 | 0.6 |
Part Number | Pairs | Nominal O.D. | Weight | Jacket Thickness | ||||||
in | mm | lb/ft | kg/m | mils | mm | |||||
Conductor Size: 16 AWG / 1.3 mm² | ||||||||||
1852-68L03A | 1 | 0.334 | 8.5 | 0.066 | 0.098 | 45 | 1.14 | |||
Conductor Size: 14 AWG/ 2.1 mm² | ||||||||||
1852-48L03A | 1 | 0.364 | 9.2 | 0.083 | 0.124 | 45 | 1.14 | |||
Conductor Size: 1.5 mm² | ||||||||||
1852-N8L03A | 1 | 0.342 | 8.7 | 0.069 | 0.103 | 45 | 1.14 |