1880 - 300 Volt, PVC, Multi Triad, Overall Shield, Unarmored
Description
- Conductor7-strand bare copper, Class B
- Primary insulation0.015 inch (0.4 mm) for 20 - 16 AWG; 0.020 inch (0.5 mm) for 14 AWG and larger, 105C FR-PVC
- Color codeBlack, white and red
- Group identificationEach triad numbered
- Overall shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
- JacketBlack FR-PVC
- Communications wire22 AWG copper, color-coded orange
Application
- Signal transmission
- UL listed as PLTC/ITC
- Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
- NEC Article 725/727
- 300 volt rated insulation
Bending Radius
- 6 x d (d = overall diamter)
Cable Type
- Multiple triad overall shield
Other Options
- Manufactured in accordance with UL. Also available to ICEA, IEC, BS standards or customized configurations.
- Various metric and AWG size conductors
- Special color coding of insulation and jacket materials
The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.