1C52 - 600 Volt, PVC / Nylon, Single Pair, Overall Shield, Unarmored
Description
- Conductor7-strand bare copper, Class B
- Primary insulation0.015 inch (0.4 mm) PVC; 0.004 inch (0.1 mm) nylon
- Color codeBlack and white
- Pair shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
- JacketBlack FR-PVC
Application
- Offers resistance to a wide range of chemicals, including acids, alkalies, alcohol, petroleum and mineral oils
- UL listed as TC per NEC Article 336
- Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
- 600 volt rated insulation
Bending Radius
- 6 x d (d = overall diameter)
Cable Type
- Single pair shielded
Other Options
- Manufactured in accordance with UL. Also available to CSA, ICEA standards or customized configurations.
- Various metric and AWG size conductors
- Special color coding of insulation and jacket materials
- Pairs color-coded black and red
- Tinned copper conductors
The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.
Electrical Properties | Units | Conductor Size | |||||||
18 AWG / 0.8 mm²2 | 16 AWG / 1.3 mm²2 | 14 AWG / 2.1 mm² | |||||||
Resistance [R] | Ω/Mft | Ω/km | 6.7 | 21.9 | 4.2 | 13.7 | 2.6 | 8.6 | |
Mutual Capacitance | |||||||||
Type 1C52 | pF/ft | pF/m | 49 | 161 | 56 | 184 | 64 | 210 | |
L/R Ratio | μH/Ω | 13 | 21 | 31 | |||||
Inductance [L] | μH/ft | μH/m | 0.19 | 0.62 | 0.18 | 0.58 | 0.17 | 0.54 |
Part Number | Pairs | Nominal O.D. | Weight | Jacket Thickness | ||||||
in | mm | lb/ft | kg/m | mils | mm | |||||
Conductor Size: 18 AWG / 0.82 mm² | ||||||||||
1C52-87000 | 1 | 0.274 | 7.0 | 0.047 | 0.069 | 45 | 1.14 | |||
Conductor Size: 16 AWG / 1.3 mm² | ||||||||||
1C52-67000 | 1 | 0.298 | 7.6 | 0.058 | 0.086 | 45 | 1.14 | |||
Conductor Size: 14 AWG / 2.1 mm² | ||||||||||
1C52-47000 | 1 | 0.328 | 8.3 | 0.075 | 0.111 | 45 | 1.14 |