1C62 - 600 Volt, PVC / Nylon, Single Triad, Overall Shield, Unarmored
Description
- Conductor7-strand bare copper, Class B
- Primary insulation0.015 inch (0.4 mm) PVC; 0.004 inch (0.1 mm) nylon
- Color codeBlack, red and white
- Triad shield100% coverage, an aluminum-polyester tape shield and a 7-strand tinned copper drain wire
- JacketBlack FR-PVC
Application
- Offers resistance to a wide range of chemicals, including acids, alkalies, alcohol, petroleum and mineral oils
- UL listed as TC per NEC Article 336
- Suitable for Class I, Division 2 and Class II, Division 2 hazardous areas
- 600 volt rated insulation
Bending Radius
- 6 x d (d = overall diameter)
Cable Type
- Single triad shielded
Other Options
- Manufactured in accordance with UL. Also available to CSA, ICEA standards or customized configurations.
- Various metric and AWG size conductors
- Special color coding of insulation and jacket materials
- Triads color-coded black, red and blue
- Tinned copper conductors
The specifications listed above are subject to change without notice. In any change, the product's performance will remain the same, or be improved.
Electrical Properties | Units | Conductor Size | |||||||
18 AWG / 0.8 mm²2 | 16 AWG / 1.3 mm²2 | 14 AWG / 2.1 mm² | |||||||
Resistance [R] | Ω/Mft | Ω/km | 6.7 | 21.9 | 4.2 | 13.7 | 2.6 | 8.6 | |
Mutual Capacitance | |||||||||
Type 1C62 | pF/ft | pF/m | 49 | 161 | 56 | 184 | 64 | 210 | |
L/R Ratio | μH/Ω | 13 | 21 | 31 | |||||
Inductance [L] | μH/ft | μH/m | 0.19 | 0.62 | 0.18 | 0.58 | 0.17 | 0.54 |
Part Number | Triads | Nominal O.D. | Weight | Jacket Thickness | ||||||
in | mm | lb/ft | kg/m | mils | mm | |||||
Conductor Size: 18 AWG / 0.82 mm² | ||||||||||
1C62-87000 | 1 | 0.288 | 7.3 | 0.057 | 0.085 | 45 | 1.14 | |||
Conductor Size: 16 AWG / 1.3 mm² | ||||||||||
1C62-67000 | 1 | 0.314 | 8.0 | 0.071 | 0.106 | 45 | 1.14 | |||
Conductor Size: 14 AWG / 2.1 mm² | ||||||||||
1C62-47000 | 1 | 0.347 | 8.8 | 0.094 | 0.140 | 45 | 1.14 |